Moulded Case Circuit Breaker

  • Rated current: 10A-630A
  • Rated operational voltage: Up to 415V
  • Rated insulation voltage: 800V
  • Impulse withstand voltage: 8kV
  • Unique feature: Overload alarm (non-trip) function
  • Referenced standards: IEC 60947-1 / IEC 60947-2
  • Best fit: Circuits requiring overload warning without power cut
Describe Display

The HM1 series is a plastic-shell moulded case circuit breaker. Its rated operating voltage is up to 415V, rated insulation voltage up to 800V, rated impulse withstand voltage up to 8kV, and rated current ranges from 10A to 630A.

This circuit breaker is suitable for power distribution, motor protection, and fire protection applications. It features an overload alarm (no-trip) function: when the line is overloaded, the breaker with this function will not trip but only output an overload signal. This ensures the continuity of power supply.

The breaker provides overload, short-circuit, and undervoltage protection to prevent damage to lines and power devices. It complies with IEC60947-1 and IEC60947-2 standards.

Quality & Compliance

  • IEC60947‑1 & IEC60947‑2 certified – international standard for low‑voltage switchgear and controlgear.
  • High breaking capacity up to 50kA (Icu) with 100% Ics options, ensuring selective coordination.
  • Built with high‑grade insulation materials (plastic shell) for durability and arc flash protection.
  • Unique overload alarm (non‑trip) function – ideal for critical power supplies where continuity is paramount (e.g., hospitals, data centers).
  • Manufactured under ISO 9001 quality management system.
Specifications

Key Specifications – HM1 Series

Rated current range 10A – 630A (multiple frame sizes)
Rated operating voltage (Ue) 415V AC
Rated insulation voltage (Ui) 800V (125 frames: 600V)
Rated impulse withstand voltage (Uimp) 8kV
Ultimate breaking capacity (Icu) 15kA – 50kA (depending on frame and level)
Service breaking capacity (Ics) 75% – 100% of Icu (12kA – 35kA)
Number of poles 1P, 2P, 3P, 4P (frame dependent)
Compliance IEC60947-1, IEC60947-2

Detailed Model Ratings & Breaking Capacities

Type Poles Rated current (A) Operating voltage (V) Insulation voltage Ui (V) Uimp (kV) Icu (kA) Ics (kA)
HM1-125M 1,2,3,4 15,25,32,40,50,63,100,125 415 600 8 15 12
1,2,3,4 25 15
HM1-125H 1,2,3,4 15,25,32,40,50,63,100,125 600 25 15
HM1-250M 1,2,3,4 125,150,160,175,200,225,250 800 25 19
1,2,3,4 35 25
HM1-250H 1,2,3,4 125,150,160,175,200,225,250 35 25
HM1-400M 3,4 300,350,400 800 35 25
50 35
HM1-400H 3,4 300,350,400 50 35
HM1-630M 3,4 500,630 35 25
50 35

Protection Functions & Features

  • Overload protection (thermal-magnetic) – long delay trip for overload.
  • Short-circuit protection (magnetic) – instantaneous trip for high fault currents.
  • Undervoltage protection – optional accessory available.
  • Overload alarm (non-trip) – outputs signal without tripping, ensuring power continuity (selectable on specific models).
  • Rotary handle / external operating mechanism – available as accessory.
Main parameters and technical performance